NFPA 70 §Article 760

Fire alarm systems

Publication
NFPA 70
Edition
2023
Section
§Article 760

What it requires

Covers both power-limited (PLFA) and non-power-limited (NPLFA) fire alarm circuits: power sources, separation from other circuits, and installation. Power-limited circuits — the usual SLC and NAC case — run listed FPL / FPLR (riser) / FPLP (plenum) cable and non-power-limited circuits run NPLFA-type cable, but as of the 2023 edition those cable listing and marking rules live in Article 722. Circuit-integrity (CI) or otherwise protected cable is required where NFPA 72 calls for survivability.