NFPA
NFPA 101 §7.9
Emergency lighting (means of egress)
- Publication
- NFPA 101
- Edition
- 2024
- Section
- §7.9
What it requires
Means-of-egress emergency lighting performance: initial 1 fc average / 0.1 fc minimum at the egress path, dropping to 0.6 / 0.06 over 90 minutes from a battery or on-site generator. Coordination citation when an egress-illumination scope intersects with the architectural lighting design.