Skip to content

NFPA

NFPA 72 §18.4

Audible notification appliances

Publication
NFPA 72
Edition
2022
Section
§18.4

What it requires

Public-mode audible signals must be at least 15 dBA above average ambient or 5 dBA above the maximum sound level having a duration of at least 60 seconds, and the combined level must not exceed 110 dBA at the minimum hearing distance.