NFPA 72 §24.3.14
Pathway survivability for emergency communications systems
- Publication
- NFPA 72
- Edition
- 2022
- Section
- §24.3.14
What it requires
Survivability is not the same thing as circuit class. A system employing relocation or partial evacuation requires Level 2 or Level 3 pathway survivability — typically 2-hour circuit-integrity (CI) cable, a 2-hour rated enclosure, or the alternatives the code allows in a fully sprinklered building. General-evacuation systems have no survivability requirement of their own.