NFPA
NFPA 72 §7.4.6
Shop drawings — system riser diagrams
- Publication
- NFPA 72
- Edition
- 2022
- Section
- §7.4.6
What it requires
A system riser diagram shall be coordinated with the floor plans and shall show, where applicable: the general arrangement in building cross-section; the number of risers; the type and number of circuits in each riser; the type and number of devices on each circuit per floor; the number of conductors per circuit; the pathway CLASS designation per Section 12.3, including the location of any end-of-line supervisory or power devices the selected class requires; and the pathway SURVIVABILITY level per Section 12.4, indicating where survivability is provided.